VSD SAVINGS CALCULATOR FOR FANS
References and Equations
References:
![]() |
For the energy savings analysis, this tool used power curves developed from data obtained by measuring the operating characteristics of various fans and from information provided in "Flow Control", a Westinghouse publication, Bulliten B-851, F/86/Rev-CMS 8121. The curves are representative, not precise. Final economic analysis should be based on actual power (kW) measurements of the pumping system. |
Constants:
Conversion Constant (kW/hp) = 0.746
Polynomial Coefficients A1, A2, A3 and A4:
Polynomial Coefficients A1, A2, A3 and A4:
Fan Type | A1 | A2 | A3 | A4 |
1 | 20.00000 | 0.06808 | -0.00128 | 0.00009 |
2 | 47.26190 | 0.67944 | -0.01554 | 0.00014 |
3 | 50.25833 | 0.71648 | -0.01452 | 0.00013 |
4 | 20.41905 | 0.10983 | 0.00745 | 0.00000 |
5 | 55.92857 | -0.56905 | 0.02462 | -0.00014 |
6 | 16.39683 | -0.05647 | 0.01237 | -0.00003 |
VSD | 5.90000 | -0.19567 | 0.00766 | 0.00004 |
Equations:
Power at Design CFM = Nameplate Horsepower × Conversion Constant (kW/hp) × Motor Load at Design CFM / Nameplate Efficiency
Computed for each capacity level:
Percent of Design kW = A1 + (A2 × Capacity) + (A3 × (Capacity2)) + (A4 × (Capacity3))
Percent of Design kW for VSD = A1 + (A2 × Capacity) + (A3 × (Capacity2)) + (A4 × (Capacity3))
Percent of Design kW = A1 + (A2 × Capacity) + (A3 × (Capacity2)) + (A4 × (Capacity3))
Percent of Design kW for VSD = A1 + (A2 × Capacity) + (A3 × (Capacity2)) + (A4 × (Capacity3))
Current Power (kW) = Percent of Design kW × (Power at Design CFM / 100)
VSD Power (kW) = Percent of Design kW for VSD × (Power at Design CFM / 100)
VSD Power (kW) = Percent of Design kW for VSD × (Power at Design CFM / 100)
Current Energy (kWh) = Current Power (kW) × (Percent of time at this Capacity / 100) × Operating Hours
VSD Energy (kWh) = VSD Power (kW) × (Percent of time at this Capacity / 100) × Operating Hours
VSD Energy (kWh) = VSD Power (kW) × (Percent of time at this Capacity / 100) × Operating Hours
Current Annual Energy Use = sum of all Current Energy (kWh)
VSD Annual Energy Use = sum of all VSD Energy (kWh)
Annual Energy Savings = Current Annual Energy Use – VSD Annual Energy Use
Annual Cost Savings = Annual Energy Savings × Cost of Electricity
VSD Annual Energy Use = sum of all VSD Energy (kWh)
Annual Energy Savings = Current Annual Energy Use – VSD Annual Energy Use
Annual Cost Savings = Annual Energy Savings × Cost of Electricity
VSD Savings Calculator For Fans
Nameplate Horsepower | hp | Annual Operating Hours | hp | |||||||||||||||||||||||||||||||||||||||||
Nameplate Efficiency | % | Fan Type | ||||||||||||||||||||||||||||||||||||||||||
Motor Load at Fan Design CFM | % | Cost of Electricity | RM/kWh | |||||||||||||||||||||||||||||||||||||||||
Duty Cycle | ||||||||||||||||||||||||||||||||||||||||||||
|
||||||||||||||||||||||||||||||||||||||||||||
Energy and Cost savings | ||||||||||||||||||||||||||||||||||||||||||||
Current Annual Energy use | kWh/yr | |||||||||||||||||||||||||||||||||||||||||||
VSD Annual Energy Use | kWh/yr | |||||||||||||||||||||||||||||||||||||||||||
Annual Energy Savings | kWh/yr | |||||||||||||||||||||||||||||||||||||||||||
Annual Cost Savings | RM/yr |